Wago 750 Series PLCs with firmware version 10 and prior include a remote attack may take advantage of an improper implementation of the 3 way handshake during a TCP connection affecting the communications with commission and service tools. Specially crafted packets may also be sent to Port 2455/TCP/IP, used in Codesys management software, which may result in a denial-of-service condition of communications with commissioning and service tools.
750-889_firmware
CVE-2020-12516
Older firmware versions (FW1 up to FW10) of the WAGO PLC family 750-88x and 750-352 are vulnerable for a special denial of service attack.
CVE-2020-12505
Improper Authentication vulnerability in WAGO 750-8XX series with FW version <= FW07 allows an attacker to change some special parameters without authentication. This issue affects: WAGO 750-852, WAGO 750-880/xxx-xxx, WAGO 750-881, WAGO 750-831/xxx-xxx, WAGO 750-882, WAGO 750-885/xxx-xxx, WAGO 750-889 in versions FW07 and below.
CVE-2019-10712
The Web-GUI on WAGO Series 750-88x (750-330, 750-352, 750-829, 750-831, 750-852, 750-880, 750-881, 750-882, 750-884, 750-885, 750-889) and Series 750-87x (750-830, 750-849, 750-871, 750-872, 750-873) devices has undocumented service access.
CVE-2021-34581
Missing Release of Resource after Effective Lifetime vulnerability in OpenSSL implementation of WAGO 750-831/xxx-xxx, 750-880/xxx-xxx, 750-881, 750-889 in versions FW4 up to FW15 allows an unauthenticated attacker to cause DoS on the device.
CVE-2021-21000
On WAGO PFC200 devices in different firmware versions with special crafted packets an attacker with network access to the device could cause a denial of service for the login service of the runtime.