An exploitable denial-of-service vulnerability exists in the IPv4 functionality of Allen-Bradley MicroLogix 1100 Programmable Logic Controller Systems Series B FRN 16.000, Series B FRN 15.002, Series B FRN 15.000, Series B FRN 14.000, Series B FRN 13.000, Series B FRN 12.000, Series B FRN 11.000 and Series B FRN 10.000. A specially crafted packet can cause a major error, resulting in a denial of service. An attacker can send a malicious packet to trigger this vulnerability.
rockwellautomation
CVE-2019-10954
An attacker could send crafted SMTP packets to cause a denial-of-service condition where the controller enters a major non-recoverable faulted state (MNRF) in CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact GuardLogix 5370 Controllers Versions 20 to 30.014 and earlier.
CVE-2019-10970
In Rockwell Automation PanelView 5510 (all versions manufactured before March 13, 2019 that have never been updated to v4.003, v5.002, or later), a remote, unauthenticated threat actor with access to an affected PanelView 5510 Graphic Display, upon successful exploit, may boot-up the terminal and gain root-level access to the device’s file system.
CVE-2019-10955
In Rockwell Automation MicroLogix 1400 Controllers Series A, All Versions Series B, v15.002 and earlier, MicroLogix 1100 Controllers v14.00 and earlier, CompactLogix 5370 L1 controllers v30.014 and earlier, CompactLogix 5370 L2 controllers v30.014 and earlier, CompactLogix 5370 L3 controllers (includes CompactLogix GuardLogix controllers) v30.014 and earlier, an open redirect vulnerability could allow a remote unauthenticated attacker to input a malicious link to redirect users to a malicious site that could run or download arbitrary malware on the user’s machine.
CVE-2019-10952
An attacker could send a crafted HTTP/HTTPS request to render the web server unavailable and/or lead to remote code execution caused by a stack-based buffer overflow vulnerability. A cold restart is required for recovering CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact GuardLogix 5370 Controllers Versions 20 to 30.014 and earlier systems.
CVE-2021-33012
Rockwell Automation MicroLogix 1100, all versions, allows a remote, unauthenticated attacker sending specially crafted commands to cause the PLC to fault when the controller is switched to RUN mode, which results in a denial-of-service condition. If successfully exploited, this vulnerability will cause the controller to fault whenever the controller is switched to RUN mode.