In Schneider Electric Wiser for KNX V2.1.0 and prior, homeLYnk V2.0.1 and prior; and spaceLYnk V2.1.0 and prior, weak and unprotected FTP access could allow an attacker unauthorized access.
schneider-electric
CVE-2018-7789
An Improper Check for Unusual or Exceptional Conditions vulnerability exists in Schneider Electric’s Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to remotely reboot Modicon M221 using crafted programing protocol frames.
CVE-2018-7790
An Information Management Error vulnerability exists in Schneider Electric’s Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to replay authentication sequences. If an attacker exploits this vulnerability and connects to a Modicon M221, the attacker can upload the original program from the PLC.
CVE-2018-7791
A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric’s Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to overwrite the original password with their password. If an attacker exploits this vulnerability and overwrite the password, the attacker can upload the original program from the PLC.
CVE-2018-7792
A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric’s Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to decode the password using rainbow table.
CVE-2018-7794
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Modicon Quantum, Modicon Premium (see security notification for specific versions) which could cause a Denial of Service when reading data with invalid index using Modbus TCP.