CVE-2022-31204

Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords. They feature a UM Protection setting that allows users or system integrators to configure a password in order to restrict sensitive engineering operations (such as project/logic uploads and downloads). This password is set using the OMRON FINS command Program Area Protect and unset using the command Program Area Protect Clear, both of which are transmitted in cleartext.
References
Link Resource
https://www.forescout.com/blog/ Third Party Advisory
https://www.cisa.gov/uscert/ics/advisories/icsa-22-179-02 Third Party Advisory US Government Resource
Configurations

Configuration 1

cpe:2.3:a:omron:cx-programmer:*:*:*:*:*:*:*:*

Information

Published : 2022-07-26 10:15

Updated : 2022-08-04 02:59


NVD link : CVE-2022-31204

Mitre link : CVE-2022-31204

Products Affected
No products.
CWE