A vulnerability has been identified in SICLOCK TC100 (All versions) and SICLOCK TC400 (All versions). Unencrypted storage of passwords in the client configuration files and during network transmission could allow an attacker in a privileged position to obtain access passwords.
A vulnerability has been identified in SICLOCK TC100 (All versions) and SICLOCK TC400 (All versions). An attacker with network access to port 69/udp could modify the administrative client stored on the device. If a legitimate user downloads and executes the modified client from the affected device, then he/she could obtain code execution on the client system.
A vulnerability has been identified in SICLOCK TC100 (All versions) and SICLOCK TC400 (All versions). An attacker with network access to port 69/udp could modify the firmware of the device.
A vulnerability has been identified in SICLOCK TC100 (All versions) and SICLOCK TC400 (All versions). An attacker with network access to the device could potentially circumvent the authentication mechanism if he/she is able to obtain certain knowledge specific to the attacked device.
A vulnerability has been identified in SICLOCK TC100 (All versions) and SICLOCK TC400 (All versions). An attacker with network access to the device could cause a Denial-of-Service condition by sending certain packets to the device, causing potential reboots of the device. The core functionality of the device could be impacted. The time serving functionality recovers when time synchronization with GPS devices or other NTP servers are completed.
A vulnerability has been identified in SIMATIC S7-400 (incl. F) CPU hardware version 4.0 and below (All versions), SIMATIC S7-400 (incl. F) CPU hardware version 5.0 (All firmware versions < V5.2), SIMATIC S7-400H CPU hardware version 4.5 and below (All versions). The affected CPUs improperly validate S7 communication packets which could cause a Denial-of-Service condition of the CPU. The CPU will remain in DEFECT mode until manual restart.
A vulnerability has been identified in Siveillance VMS Video for Android (All versions < V12.1a (2018 R1)), Siveillance VMS Video for iOS (All versions < V12.1a (2018 R1)). Improper certificate validation could allow an attacker in a privileged network position to read data from and write data to the encrypted communication channel between the app and a server. The security vulnerability could be exploited by an attacker in a privileged network position which allows intercepting the communication channel between the affected app and a server (such as Man-in-the-Middle). Furthermore, an attacker must be able to generate a certificate that results for the validation algorithm in a checksum identical to a trusted certificate. Successful exploitation requires no user interaction. The vulnerability could allow reading data from and writing data to the encrypted communication channel between the app and a server, impacting the communication's confidentiality and integrity. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.
Logo!8_bm_firmware, Logo!8_bm, Cp1604_firmware, Cp1604, Cp1616_firmware, Cp1616, Dk_standard_ethernet_controller_firmware, Dk_standard_ethernet_controller, Ek-ertec_200_firmware, Ek-ertec_200
2022-12-13
N/A
6.1 MEDIUM
A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (All versions < V5.2.3), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.4.1), SCALANCE X-200RNA switch family (All versions < V3.2.7), SCALANCE X-300 switch family (incl. X408 and SIPLUS NET variants) (All versions < V4.1.3). The integrated configuration web server of the affected devices could allow Cross-Site Scripting (XSS) attacks if unsuspecting users are tricked into accessing a malicious link. User interaction is required for a successful exploitation. The user must be logged into the web interface in order for the exploitation to succeed. At the stage of publishing this security advisory no public exploitation is known. The vendor has confirmed the vulnerability and provides mitigations to resolve it.
A vulnerability has been identified in SIMATIC WinCC OA Operator iOS App (All versions < V1.4). Insufficient protection of sensitive information (e.g. session key for accessing server) in Siemens WinCC OA Operator iOS app could allow an attacker with physical access to the mobile device to read unencrypted data from the app's directory. Siemens provides mitigations to resolve the security issue.
A vulnerability has been identified in RAPIDLab 1200 systems / RAPIDPoint 400 systems / RAPIDPoint 500 systems (All versions_without_ use of Siemens Healthineers Informatics products), RAPIDLab 1200 Series (All versions < V3.3 _with_ Siemens Healthineers Informatics products), RAPIDPoint 500 systems (All versions >= V3.0 _with_ Siemens Healthineers Informatics products), RAPIDPoint 500 systems (V2.4.X_with_ Siemens Healthineers Informatics products), RAPIDPoint 500 systems (All versions =< V2.3 _with_ Siemens Healthineers Informatics products), RAPIDPoint 400 systems (All versions _with_ Siemens Healthineers Informatics products). A factory account with hardcoded password might allow attackers access to the device over port 5900/tcp. Successful exploitation requires no user interaction or privileges and impacts the confidentiality, integrity, and availability of the affected device. At the time of advisory publication, no public exploitation of this security vulnerability is known. Siemens Healthineers confirms the security vulnerability and provides mitigations to resolve the security issue.