** REJECT ** DO NOT USE THIS CANDIDATE NUMBER. ConsultIDs: none. Reason: This candidate was withdrawn by its CNA. Further investigation showed that it was not a security issue. Notes: none.
Logo!8_bm_firmware, Logo!8_bm, Cp1604_firmware, Cp1604, Cp1616_firmware, Cp1616, Dk_standard_ethernet_controller_firmware, Dk_standard_ethernet_controller, Ek-ertec_200_firmware, Ek-ertec_200
2019-10-03
N/A
5.9 MEDIUM
A vulnerability has been identified in Firmware variant IEC 61850 for EN100 Ethernet module (All versions < V4.35), Firmware variant MODBUS TCP for EN100 Ethernet module (All versions), Firmware variant DNP3 TCP for EN100 Ethernet module (All versions), Firmware variant IEC104 for EN100 Ethernet module (All versions), Firmware variant Profinet IO for EN100 Ethernet module (All versions), SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules (All versions < V7.82), SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules (All versions < V7.58). Specially crafted packets to port 102/tcp could cause a denial-of-service condition in the affected products. A manual restart is required to recover the EN100 module functionality of the affected devices. Successful exploitation requires an attacker with network access to send multiple packets to the affected products or modules. As a precondition the IEC 61850-MMS communication needs to be activated on the affected products or modules. No user interaction or privileges are required to exploit the vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the network functionality of the device, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.
** REJECT ** DO NOT USE THIS CANDIDATE NUMBER. ConsultIDs: none. Reason: This candidate was withdrawn by its CNA. Further investigation showed that it was not a security issue. Notes: none.
Logo!8_bm_firmware, Logo!8_bm, Cp1604_firmware, Cp1604, Cp1616_firmware, Cp1616, Dk_standard_ethernet_controller_firmware, Dk_standard_ethernet_controller, Ek-ertec_200_firmware, Ek-ertec_200
2019-10-03
N/A
7.5 HIGH
A vulnerability has been identified in SIMATIC S7-300 CPUs (All versions < V3.X.16). The affected CPUs improperly validate S7 communication packets which could cause a Denial-of-Service condition of the CPU. The CPU will remain in DEFECT mode until manual restart. Successful exploitation requires an attacker to be able to send a specially crafted S7 communication packet to a communication interface of the CPU. This includes Ethernet, PROFIBUS, and Multi Point Interfaces (MPI). No user interaction or privileges are required to exploit the security vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the core functionality of the CPU, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.
** REJECT ** DO NOT USE THIS CANDIDATE NUMBER. ConsultIDs: none. Reason: This candidate was withdrawn by its CNA. Further investigation showed that it was not a security issue. Notes: none.
Aix, Z/os, Db2, Spectrum_protect, Open_power, Power_system_8335-gth, Power_system_8335-gtx, Power_system_8335-gtc, Power_system_8335-gtg, Power_system_8335-gtw
2019-10-09
N/A
6.5 MEDIUM
The IBM Java Runtime Environment's Diagnostic Tooling Framework for Java (DTFJ) (IBM SDK, Java Technology Edition 6.0 , 7.0, and 8.0) does not protect against path traversal attacks when extracting compressed dump files. IBM X-Force ID: 144882.
Logo!8_bm_firmware, Logo!8_bm, Cp1604_firmware, Cp1604, Cp1616_firmware, Cp1616, Dk_standard_ethernet_controller_firmware, Dk_standard_ethernet_controller, Ek-ertec_200_firmware, Ek-ertec_200
2019-04-18
N/A
7.5 HIGH
A vulnerability has been identified in SIMATIC S7-1500 CPU (All versions >= V2.0 and < V2.5), SIMATIC S7-1500 CPU (All versions <= V1.8.5). Specially crafted network packets sent to port 80/tcp or 443/tcp could allow an unauthenticated remote attacker to cause a Denial-of-Service condition of the device. The security vulnerability could be exploited by an attacker with network access to the affected systems on port 80/tcp or 443/tcp. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.
Logo!8_bm_firmware, Logo!8_bm, Cp1604_firmware, Cp1604, Cp1616_firmware, Cp1616, Dk_standard_ethernet_controller_firmware, Dk_standard_ethernet_controller, Ek-ertec_200_firmware, Ek-ertec_200
2019-04-18
N/A
7.5 HIGH
A vulnerability has been identified in SIMATIC S7-1500 CPU (All versions >= V2.0 and < V2.5), SIMATIC S7-1500 CPU (All versions <= V1.8.5). Specially crafted network packets sent to port 80/tcp or 443/tcp could allow an unauthenticated remote attacker to cause a Denial-of-Service condition of the device. The security vulnerability could be exploited by an attacker with network access to the affected systems on port 80/tcp or 443/tcp. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.
A vulnerability has been identified in SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1). Sending of specially crafted packets to port 102/tcp via Ethernet interface via PROFIBUS or Multi Point Interfaces (MPI) could cause a denial of service condition on affected devices. Flashing with a firmware image may be required to recover the CPU. Successful exploitation requires an attacker to have network access to port 102/tcp via Ethernet interface or to be able to send messages via PROFIBUS or Multi Point Interfaces (MPI) to the device. No user interaction is required. If no access protection is configured, no privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.
Logo!8_bm_firmware, Logo!8_bm, Cp1604_firmware, Cp1604, Cp1616_firmware, Cp1616, Dk_standard_ethernet_controller_firmware, Dk_standard_ethernet_controller, Ek-ertec_200_firmware, Ek-ertec_200
2023-01-10
N/A
7.5 HIGH
A vulnerability has been identified in SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1). Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.